Online UPS

EH5500 LV Series (AC:120V 1-3KVA)

ModelEH55 LV 1K, EH55 LV 1KS, EH55 LV 2K, EH55 LV 2KS, EH55 LV 3K, EH55 LV 3KS

Online UPS — High Frequency Single Phase Online UPS (1KVA/1KW / 2KVA/2KW / 3KVA/3KW)

At a glance

Rated Capacity
1KVA/1KW / 2KVA/2KW / 3KVA/3KW
Output voltage
100/110/115/120/127VAC

Series ranges may cover several models. Confirm your required configuration with our team.

View comparison shortlist

0 / 3 selected in this product family. Your shortlist stays in this tab.

Ask our team for current pricing and availability for this model.

Applications

Backup Power / Critical Power (UPS)

Key features

  • Double-conversion online design with zero output transfer time.
  • DSP digital control for stable, reliable performance.
  • Active power factor correction (PFC) keeps input power factor close to 1.
  • Selectable output voltage: 100/110/115/120/127VAC.
  • Ultra-wide input voltage range — accepts voltages as low as 110V without switching to battery power.
  • LCD + LED real-time display with self-diagnosis for hidden faults.
  • Cold-start capability from battery without grid input.
  • Input frequency range of 40-70Hz, compatible with fuel generators.
  • AC input over/under-voltage, output overload and short-circuit protection.
  • Output power factor up to 1.0 with efficiency up to 95%.
  • Automatic recovery and reconnection when utility power returns.
  • Standard RS232 communication port for multifunction monitoring.

Specifications 37 details

ModelsEH55 LV 1K, EH55 LV 1KS, EH55 LV 2K, EH55 LV 2KS, EH55 LV 3K, EH55 LV 3KS
Rated Capacity1KVA/1KW / 2KVA/2KW / 3KVA/3KW
Input formatL+N+PE
Rated input voltage100/110/115/120/127VAC
Voltage range55~150VAC
Frequency range50/60±6Hz (Default), ±10Hz (Settable)
Input power factor≥0.99
Input total harmonic distortion≤3% linear load ≤8% nonlinear load
Output formatL+N+PE
Output voltage100/110/115/120/127VAC
Output accuracy±1%
Output frequencyFor on-line mode: follow current frequency, battery mode: 50/60Hz±0.1%
Output harmonic distortion≤2% linear load; ≤5% nonlinear load (PF=0.8)
PF1
Overload capacityAC Mode:10min@102%~110% Load1min@110%~130% Load10s@130%~150% Load200ms@>150% LoadBattery Mode:10min@102%~110% Load1min@110%~130% Load10s@130%~150% Load200ms@>150% Load
Switch to battery mode0ms
Switch to bypass4ms
AC priority modeSupport
AC Mode (Full Load)93.5%@110VAC / 95%@110VAC / 94%@110VAC
Battery Mode for without built-in battery (Full Load)88.5%@36VDC / 91.5%@72VDC / 91.5%@96VDC
Battery Mode for with built-in battery (Full Load)89.5%@24VDC / 92.5%@48VDC / 92.5%@72VDC
Battery typeLead Acid Battery
Battery number7Ah*2/7Ah*3 / 3 / 7Ah*4/7Ah*6 / 6 / 7Ah*6/7Ah*8 / 8
Chaging currentBuilt-in battery 1K-3K: 1A (Default) 1-2A (Adjustable) Without built-in battery 1KS-3KS: 5A (Default) 1-12A (Adjustable)
Charging modeTwo-stage/three-stage charging
LCD2×8PIN/Pitch2.54mm, support 128-bit segment code, up to 4 buttons + 4 LEDs, can display operating mode / load / input / output, etc.
RS-232Support: Windwos 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC
USBWindows Famlly & MAC
Intelligent slot(Optional)SNMP/AS400 Relay Card/RS485
EPO (Optional)Support
Operating ambient temperature0~40℃
Operating environment humidity20%~95% (no condensation)
Storage temperature-15~60℃ (batteries: 0~40℃ )
AltitudeThe elevation should not exceed 1000m, 1000m or above, up to 4000 m, reference IEC62040
Noise≤45db
Dimensions (D*W*H) (mm)395*143*222 / 455*190*330 / 455*190*330
Net Weight (kg)9.5 / 5.5 / 19/23 / 5.5 / 27/31 / 10