EH5500 TLV Series (AC:110/220V 6-10KVA)

ModelEH55 TLV 6K, EH55 TLV 6KS, EH55 TLV 10K, EH55 TLV 10KS

Online UPS — High Frequency Single Phase Online UPS (6KVA/6KW / 10KVA/10KW)

At a glance

Rated Capacity
6KVA/6KW / 10KVA/10KW
Output voltage
100/110/115/120VAC; 208/220/230/240VAC

Series ranges may cover several models. Confirm your required configuration with our team.

View comparison shortlist

0 / 3 selected in this product family. Your shortlist stays in this tab.

Ask our team for current pricing and availability for this model.

Applications

Backup Power / Critical Power (UPS)

Key features

  • Double-conversion online design with zero output transfer time.
  • DSP digital control for stable, reliable performance.
  • Active power factor correction (PFC) keeps input power factor at 1.
  • Selectable output voltage across 100/110/115/120/208/220/230/240VAC.
  • Ultra-wide input voltage range — accepts voltages as low as 110V without switching to battery power.
  • LCD + LED real-time display with self-diagnosis for hidden faults.
  • Cold-start capability from battery without grid input.
  • Input frequency range of 40-70Hz, compatible with fuel generators.
  • Comprehensive protection: over/under-voltage, overload, short-circuit, temperature and battery overcharge.
  • Selectable output power factor up to 1.0 with efficiency up to 95%.
  • Standard RS232 communication port for multifunction monitoring.

Specifications 36 details

ModelsEH55 TLV 6K, EH55 TLV 6KS, EH55 TLV 10K, EH55 TLV 10KS
Rated Capacity6KVA/6KW / 10KVA/10KW
Input formatL+N+PE
Rated input voltage220/230/240VAC
Voltage range110~300VAC
Frequency range50/60±6Hz (Default), ±10Hz (Settable)
Input power factor≥0.99
Input total harmonic distortion≤4% inear load
Output formatL+N+PE
Output voltage100/110/115/120VAC; 208/220/230/240VAC
Output accuracy±1%
Output frequencyFor on-line mode: follow current frequency, battery mode: 50 / 60Hz±0.1%
Output harmonic distortion≤ 2% linear load; ≤ 5% nonlinear load (PF=0.7)
Overload capacityAC Mode:30min@102%~110% Load10min@110%~130% Load30s@130%~150% Load200ms@>150% LoadBattery Mode:1min@102%~110% Load10s@110%~130% Load3s@130%~150% Load200ms@>150% Load
Switch to battery mode0ms
Switch to bypass4ms
AC priority modeSupport
AC Mode (Full Load)Peak efficiency 95.5%, Full load efficiency 94%
Battery Mode (Full Load)Peak efficiency 94.5%, Full load efficiency 94.3% (20pcs Battery)
Battery typeLead Acid Battery
Battery number7Ah*16 / 16/18/20 (adjustable) 16 (default ) / 7Ah*16 / 16/18/20 (adjustable) 16 (default )
Chaging current1A (default) / 1-12A adjustable (default 5A)) / 1A (default) / 1-12A adjustable (default 5A))
Charging modeTwo-stage/three-stage charging
LCD2×8 PIN/Pitch 2.54mm, support 128-bit segment code, up to 4 buttons + 4 LEDs, can display operating mode / load / input / output, etc.
RS-232Support: Windows 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC
USBWindows Family & MAC
EPOSupport
Intelligent slot (Optional)SNMP/AS400 Relay Card/RS485
Maintenance bypass switch (Optional)Support
Operating ambient temperature0~40℃
Operating environment humidity20%~95%(no condensation)
Storage temperature-15~60℃ (batteries: 0~40℃ )
AltitudeThe elevation should not exceed 1000m, 1000m or above, up to 4000 m, reference IEC62040
Noise≤50db
Dimensions (D*W*H) (mm)500*250*610 / 500*250*850 / 500*250*610 / 500*250*850
Net weight (kg)93 / 59 / 102 / 60.5